FXII Chiller Revision: 05 March 25, 2013 6
OVER CURRENT: The total system run current exceeded the limit set in the
programmable parameters. Systems may start with currents exceeding the limit but must
be below the limit within two seconds after the start of the compressor.
FREEZE FAULT: The closed circulating loop water temperature at the water
outlet sensor is below 34°F. This fault causes an immediate lockout for system
protection.
FLOW SWITCH OPEN: The closed circulating water loop flow switch connected
to the service input is open for more than 10 seconds. When this fault occurs, all outputs
will shut down for two minutes then restart.
SENSOR TROUBLE WATER IN: The sensor connected to the ALT AIR jack
(Loop water in) has failed or is disconnected.
SENSOR TROUBLE WATER OUT: The sensor connected to the OUTSIDE jack
(Loop water out) has failed or is disconnected.
HIGH LIMIT: Closed circulating loop water outlet temperature has exceeded the
limit set in the programmable parameters.
KLIXON OPEN: EasyStart has detected a problem with the compressor most
likely an open compressor overload protector. EasyStart will wait 3 minutes before
attempting a restart. Systems without EasyStart should set the program parameter “Starter
Present” to “NO” to prevent this error.
COMPRESSOR STALLED: EasyStart has detected a problem with the
compressor most likely a stalled compressor. EasyStart will wait 3 minutes before
attempting a restart. Systems without EasyStart should set the program parameter “Starter
Present” to “NO” to prevent this error.